Halogen-free plastic-sheathed cable with enhanced characteristics in case of fire, acc. to DIN VDE 0250-214
Julat suhu semasa pemasangan +5°C hingga +70°C pemasangan tetap -30°C hingga +70°C
Maks. suhu pada konduktor semasa operasi +70°C sekiranya litar pintas +250°C
Voltan nominal U0/U 300/500 V
Uji voltan 2000 V
Jejari lentur minimum pemasangan tetap 4x luar Ø
Caloric load values see "Technical Information"
Struktur kabel:
Bare copper conductor, acc. to DIN VDE 0295 / IEC 60228 ≤ 10 mm² cl.1: single wire ≥ 16 mm² cl.2: multi wire
Penebat teras polietilena silang silang (XLPE)
Core identification acc. to DIN VDE 0293-308 1 core: black or green-yellow ≤ 5 cores: coloured ≥ 6 cores: black with continuous white numbering
Teras terdampar dalam lapisan dengan panjang lay optimum
Overall core sheath of halogen-free filling compound (may be omitted for single core cables)
Outer sheath of flame-retardant, halogen-free polymer compound type HM2 acc. to DIN VDE 0207-24 Sheath colour: grey (RAL 7035)
Properties:
Tahan api
Bebas halogen, tiada pemisahan gas menghakis dan toksik
Penyebaran api terhad
Pembangunan asap rendah
Tahan ozon
ujian:
Flame test acc. to DIN VDE 0482-332-3-24 / DIN EN 60332-3-24 / IEC 60332-3-24
Kekakisan gas pembakaran acc. kepada DIN VDE 0482-754-2 / DIN EN 60754-2 / IEC 60754-2
Acc bebas halogen kepada DIN VDE 0482-754-1 / DIN EN 60754-1 / IEC 60754-1
Smoke density acc. to DIN VDE 0482-1034-1+2 / DIN EN 61034-1+2 / IEC 61034-1+2
Ozone resistant acc. to DIN VDE 0473-811-403/DIN EN 60811-403
LS0H = Halogen Sifar Asap Rendah
Konduktor dibina secara metrik (mm²). Penamaan AWG adalah anggaran dan bermaklumat semata-mata.
Catatan:
re = round conductor, single wire rm = round conductor, multi wire
Also deliverable in screened (St) version.
Permohonan:
Halogen-free plastic-sheathed cables with enhanced characteristics in case of fire are used for applications where harm to human life and damage to property must be prevented in the event of fire, e. g. in industrial installations, communal establishments, hotels, airports, underground stations, railway stations, hospitals, departmental stores, banks, schools, theatres, multi-storey buildings, process control centres etc. Suitable for installation in dry, damp or wet environments, for installation above, on, in and beneath plaster as well as in masonry walls and in concrete, not however for direct embedding in vibration, compacted or tamped concrete.
CE = Produk mematuhi Arahan Voltan Rendah 2014/35/EU.