model |
10KS |
15KS |
20KS |
|
capacity* |
10000VA / 8000W |
15000VA / 12000W |
20000VA / 16000W |
|
Input |
||||
voltage range |
Minimum switching voltage |
110 VAC(L-N) ± 3% at 50% load 176 VAC(L-N) ± 3% at 100% load |
||
Minimum recovery voltage |
Minimum loss voltage + 10V |
|||
Maximum switching voltage |
300 VAC(L-N) ± 3% at 50% load 276 VAC(L-N) ± 3% at 100% load |
|||
Maximum recovery voltage |
Maximum loss voltage-10V |
|||
Frequency Range |
46Hz ~ 54 Hz @ 50Hz system 56Hz ~ 64 Hz @ 60Hz system |
|||
Phase |
Three-phase grounding |
|||
Power Factor |
≧ 0.99 at 100% load |
|||
Output |
||||
output voltage |
208/220/230/240VAC |
|||
AC voltage range |
± 1% |
|||
Frequency range (synchronization range) |
46Hz ~ 54 Hz @ 50Hz system; 56Hz ~ 64 Hz @ 60Hz system |
|||
Frequency range (battery mode) |
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz |
|||
overload |
AC mode |
100%~110%: 10 minutes 110%~130%: 1 minutes >130% : 1 second |
||
Battery mode |
100%~110%: 30 second 110%~130%: 10 second >130% : 1 second |
|||
Current peak ratio |
3:1 max |
|||
Harmonic distortion |
≦ 2% @ 100% linear load; ≦ 5% @ 100% nonlinear load |
|||
Switching time |
Online←→Battery |
0 ms |
||
Inverter←→Bypass |
0 ms |
|||
Inverter←→ECO |
<10 ms |
|||
effectiveness |
||||
AC mode |
> 89% |
>89% |
>89% |
|
Battery mode |
> 86% |
>88% |
>87% |
|
Battery |
||||
Standard machine |
model |
12 V / 9 Ah |
12 V / 9 Ah |
12 V / 9 Ah |
number |
20 |
2 x 20 |
2 x 20 |
|
Charging time |
90% capacity in 9 hours |
|||
Charging current (maximum) |
1.0 A ± 10% |
2.0 A ± 10% |
2.0 A ± 10% |
|
Charging voltage |
273 VDC ± 1% (based on 20 batteries) |
|||
Long extension machine |
model |
Varies according to usage |
||
number |
18 - 20 |
|||
Charging current (maximum) |
4.0 A ± 10% |
4.0 A ± 10% |
4.0 A ± 10% |
|
Charging voltage |
273 VDC ± 1% (based on 20 batteries) |
|||
Exterior |
||||
Standard machine |
Dimensions, (D*W*H)(mm) |
UPS host: 668 x 438 x 133[3U] Battery box: 580 x 438 x 133[3U] |
UPS host: 668 x 438 x 266[6U] Battery box: 580 x 438 x 133[3U] x 2 pcs |
|
Net weight (kgs) |
UPS host: 22 Battery box: 63 |
UUPS host: 45 Battery box: 63 x 2 pcs |
||
Long extension machine |
Dimensions, (D*W*H)(mm) |
668 x 438 x 133[3U] |
668 x 438 x 266[6U] |
668 x 438 x 266[6U] |
Net weight (kgs) |
22 |
45 |
45 |
|
Environmental conditions |
||||
Operating temperature |
0 ~ 40°C (battery life will be shortened in an environment> 25°C) |
|||
Operating humidity |
<95% without condensation |
|||
Operating altitude** |
<1000m |
|||
noise |
Less than 58dB @ 1 Meter |
Less than 60dB @ 1 Meter |
||
management |
||||
Smart RS-232 or USB |
Support Windows® 2000/2003/XP/Vista/2008/7/8, Linux and MAC |
|||
Optional SNMP |
Support for power management by SNMP administrator and web browser |